System data | CANopen | BK5120 |
---|
Number of I/O stations | 64 (BK5120: 255 with K-bus extension) |
Number of I/O points | depends on the structure |
Data transfer medium | screened, twisted copper cableИли отправьте нам запрос наecommended) |
Max. cable length | 5,000 m | 2,500 m | 1,000 m | 500 m | 250 m | 100 m | 40 m |
|
Data transfer rates | 10 kbaud | 20 kbaud | 50 kbaud | 100/125 kbaud | 250 kbaud | 500 kbaud | 1,000 kbaud |
|
PDO modes | synchron, cyclic, event driven, polling |
Technical data | BK5120 |
---|
Number of Bus Terminals | 64 (255 with K-bus extension) |
Max. number of bytes fieldbus | 16 Tx/Rx PDOs |
Digital peripheral signals | 960 inputs/outputs |
Analog peripheral signals | 60 inputs/outputs |
Configuration possibility | via KS2000 or the controller |
Number of PDOs (CANopen) | 16 Tx/16 Rx |
Additional CANopen features | life, node guarding, emergency object, variable mapping, store/restore |
Data transfer rates | up to 1 Mbaud |
Bus interface | 1 x open style connector, 5-pin, included |
Power supply | 24 V DC (-15 %/+20 %) |
Input current | 70 mA + (total K-bus current)/4, 500 mA max. |
Starting current | approx. 2.5 x continuous current |
Recommended fuse | ≤ 10 A |
Current supply K-bus | 1750 mA |
Power contacts | 24 V DC max./10 A max. |
Electrical isolation | 500 V (power contact/supply voltage Bus Coupler) |
Weight | approx. 150 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Approvals | CE, UL, Ex, GL |