Описание оборудования | |
---|---|
PROFIBUS Gateway with integrated Safety Monitor, double master for 2 AS-Interface networks | |
General specifications | |
AS-Interface specification | V3.0 |
PLC-Functionality | activateable |
Duplicate address detection | from AS-Interface slaves |
Earth fault detection | integrated |
EMC monitoring | integrated |
Diagnostics function | Extended function via display |
Switch-on delay | < 10 s |
Response delay | < 40 ms |
UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 3 |
Performance level (PL) | PL e |
MTTFd | 200 a |
B10d | 2 E+7 |
Indicators/operating means | |
Display | Illuminated graphical LC display for addressing and error messages |
LED PROFIBUS | PROFIBUS master detected; LED green |
LED AS-i ACTIVE | AS-Interface operation normal; LED green |
LED CONFIG ERR | configuration error; LED red |
LED PRG ENABLE | autom. programming; LED green |
LED POWER | voltage ON; LED green |
LED PRJ MODE | projecting mode active; LED yellow |
LED U AS-i | AS-Interface voltage; LED green |
LED AUX | ext. auxiliary voltage UAUX ; LED green |
LED EDM/Start | External device monitoring circuit inputs closed, 4x yellow LEDs |
LED output circuit | Output circuit closed; 4 x green LEDs |
Button | 4 |
Electrical specifications | |
Insulation voltage | ? 500 V |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24VDC |
Rated operating current | ? 300mA off AS interface network 1 ? 70mA off AS interface network 2 |
Interface 1 | |
Interface type | RS-485 |
Protocol | PROFIBUS DP V1 |
Transfer rate | 9.6 kBit/s / 12 MBit/s , Automatic baud rate detection |
Interface 2 | |
Interface type | RS 232, serial Diagnostic Interface |
Transfer rate | 19,2 kBit/s |
Interface 3 | |
Interface type | Chip card slot |
Input | |
Number/Type | 4 EDM/Start inputs: EDM: Inputs for the external device monitoring circuits Start: start inputs: Static switching current 4mA at 24V, dynamic 30mA at 24V (T=100?s) |
Output | |
Safety output | Output circuits 1 and 2: 2 potential-free contacts, max. contact load: 3 ADC-13 at 30VDC, 3AAC-15 at 30VAC Output circuits 3 and 4: 2 PNP transistor outputs max. contact load: 0.5 ADC-13 at 30 VDC |
Connection | |
PROFIBUS | Sub-D interface |
AS-Interface | spring terminals, removable |
Directive conformity | |